LS-EVW Explosion Vent Window
Opaque composite sash · Controlled washer release · Multi-unit vent wall
LS-EVW combines an opaque metal-composite sash with LS-EV01 explosion vent fasteners. Controlled washer rupture releases the sash fixing points to form a vent opening; multiple units can form a window-type explosion vent wall.
Illustrative vent-wall arrangement. Final unit layout follows the project design.
FM Approved Release Component
LS-EVW uses the LS-EV01 release fastener approved under FM Approvals Class 4440. The complete window configuration follows the project's venting and wind-load design. FM 1-44 and FM 1-28 are applied as project design references.
Sash construction and project specifications
18 mm thickness · 16 kg/m³ density
LS-EV01 FM Approved washer · 700 N nominal rupture force per washer
Coordinated with local design wind speed, wind pressure and vent design; actual value and tolerance require project approval.
Calculated from actual materials and construction and included in the vent design calculation.
Electrostatic powder coating ≥80 μm · Colour confirmed per project
Matched LS-EV01 Washer and Screw
A thin aluminium washer bonded to a black neoprene backing releases sash fixing points through controlled rupture. Screws remain anchored after sash release.
The controlled-release washer is paired with the specified M6.3 screw. Refer to the current approved component drawing for dimensions and installation details.
Matched screw: 6.3 mm (0.25 in) diameter · T30 pan-head self-drilling screw. Length and drill-point type follow the substrate and approved design.
700 N is the nominal rupture force per washer. Panel or window release pressure is determined and verified through the project design, including fastener quantity, position and loaded area.
Project Design Parameters
FM 1-44: calculate vent area and release pressure from the hazardous material, space dimensions, sash mass and structural pressure resistance.
FM 1-28: assess positive and negative wind pressures and wall pressure zones using local design wind speed and exterior-wall conditions.
FM 4440: performance testing, approval and selection reference for venting systems and fasteners; the identified approved release component is LS-EV01.
Opening pressure, effective vent area, sash mass and fastener layout are calculated and verified for the installation. Structural pressure resistance and local positive and negative wind loads are coordinated in the project design. Applicable FM 1-44 and FM 1-28 criteria, document editions and design conditions are confirmed during design and submission.
If wind-load and venting requirements cannot both be met, reassess the system configuration and applicable design method.
Selection and approval questions
Is the complete LS-EVW window FM Approved?
FM approval identified in the supplied documentation applies to the LS-EV01 release component. The complete LS-EVW configuration requires project-specific design approval; component approval should not be presented as separate approval of the complete window.
Does 700 N determine the opening pressure of every window?
No. 700 N is the nominal rupture force per washer. Complete-window opening pressure depends on fastener layout and loaded area and must be coordinated with sash mass, vent requirements, structural resistance and wind loads.
Is LS-EVW a transparent or everyday ventilation window?
The documented product is an opaque metal-composite sash with a glass-wool core, designed to create an explosion vent opening by controlled release. The source does not describe a transparent daylighting window or a routine ventilation product.
Can multiple units form a vent wall?
Yes. Unit dimensions, quantity and location are configured per project. Their total effective vent area must satisfy the calculated requirement, with approved pressure settings, fastener arrangements and safety devices.